Digiplex -EVO- - 53 - Programming Guide
Contact ID Report Code List
If using the Ademco Contact ID format, key in the 2-digit hexadecimal value (PROG. VALUE) to program the desired report codes into sections [0201] to
[0296], [0701] to [0832], [2001] to [2199], and [3900] to [3999].
Module TLM restore 3 352 - Telco 2 fault restore LR - Phone Line Restoral
Early to Arm by User 3 451 - Early to Close CK - Early to Close
Late to Arm by User 3 452 - Late to Close CJ - Late to Close
Zone Excluded on Force Arming 1 57A - Zone Bypass XW - Zone Forced
Zone Went Back to Arm Status 3 57A - Zone Bypass Restore VV - Zone Included
Printer fault restore 3 336 - Local printer failure restore VR - Printer Restore
Module AC restore 3 3A1 - AC loss restore AR - AC Restoral
Module battery restore 3 3A9 - Battery test failure restore YR - System Battery Restoral
Module Auxiliary supply restore 3 3AA - System trouble restore YQ - Power Supply Restored
Fail to communicate with monitoring station 1 354 - Fail to communicate YC - Communication Fails
Module RF low battery 1 384 - RF transmitter low battery XT - Transmitter Battery Trouble
Module RF supervision trouble 1 381 - Loss of supervision - RF US - Untype Zone Supervision
Module RF battery restore 3 384 - RF transmitter battery restore XR - Transmitter Battery Restoral
Module RF supervision restore 3 381 - Supervision restore - RF UR - Untyped Zone Restoral
Cold Start 1 3A8 - System shutdown RR - Power Up
Warm Start 1 3A5 - System reset YW - Watchdog Reset
Test Report engaged 1 6A2 - Periodic test report TX - Test Report
Listen-In request 1 606 - Listen-In to follow LF - Listen-In to follow
WinLoad Login request 1 411 - Call Back Request RB - Remote Program Begin
PC software communication finished 1 412 - Successful - download access RS - Remote Program Success
Installer on site 1 627 - Program mode Entry LB - Local Program
Installer programming finished 1 628 - Program mode Exit LS - Local Program Success
Module Fail to Communicate Restore 3 354 - Fail to Communicate Restore YK - Communication Restore
CID# Reporting Code
Prog.
Value
CID# Reporting Code
Prog.
Value
CID# Reporting Code
Prog.
Value
MEDICAL ALARMS - 100 BURGLAR ALARMS - 130 150 24-Hour Non-Burglary 25
100 Medical Alarm 01 130 Burglary 13 151 Gas Detected 26
101 Personal Emergency 02 131 Perimeter 14 152 Refrigeration 27
102 Fail to Report In 03 132 Interior 15 153 Loss of Heat 28
FIRE ALARMS - 110 133 24-Hour 16 154 Water Leakage 29
110 Fire Alarm 04 134 Entry/Exit 17 155 Foil Break 2A
111 Smoke 05 135 Day/Night 18 156 Day Trouble 2B
112 Combustion 06 136 Outdoor 19 157 Low Bottled Gas Level 2C
113 Water Flow 07 137 Tamper 1A 158 High Temperature 2D
114 Heat 08 138 Near Alarm 1B 159 Low Temperature 2E
115 Pull Station 09 139 Intrusion Verifier 1C 161 Loss of Air Flow 2F
116 Duct 0A GENERAL ALARMS - 140 162 Carbon Monoxide Detected 30
117 Flame 0B 140 General Alarm 1D 163 Tank Level 31
118 Near Alarm 0C 141 Polling Loop Open 1E FIRE SUPERVISORY - 200 & 210
PANIC ALARMS - 120 142 Polling Loop Short 1F 200 Fire Supervisory 32
120 Panic Alarm 0D 143 Expansion Module Failure 20 201 Low Water Pressure 33
121 Duress 0E 144 Sensor Tamper 21 202 Low CO2 34
122 Silent 0F 145 Expansion Module Tamper 22 203 Gate Valve Sensor 35
123 Audible 10 146 Silent Burglary 23 204 Low Water Level 36
124 Duress-Access Granted 11 147 Sensor Supervision Failure 24 205 Pump Activated 37
125 Duress-Egress Granted 12 24-HOUR NON-BURGLARY - 150 & 160 206 Pump Failure 38
System Event
Default Contact ID Report Code
when using sections [4032] to [4037]
Default SIA Report Code
when using sections [4032] to [4037]